Benjamin James Bickerton
Published: 2012
Total Pages: 356
Get eBook
ABSTRACT CONT'D: Charge analysis parameters zeta potential and streaming current were found to have a strong correlation in bench-scale testing, though the relationship between the two was affected by the coagulation pH. The results suggest that utilizing streaming current for coagulant dose control at a full-scale WTP would be best accomplished by establishing a consistent relationship between raw water quality, pH and other factors with streaming current experimentally before relying streaming current targets for dose control. Equivalent or improved DAF efficacy for solid-liquid separation was found when the recycle rate was lowered from 12 to 6 % in bench-scale tests and 12 to 8% in full-scale tests. The results suggested that maintaining an optimum air:solids ratio improved treatment performance, possibly by providing adequate bubble contact opportunities while minimizing excess shearing of the sludge blanket. The most significant finding of this research was that maintaining the coagulation pH in WTPs utilizing PACl coagulants is of utmost importance during source water quality deterioration in order to optimize treatment performance as well as prevent excess dissolved and precipitated aluminum from entering a public drinking water supply.